Non-return Valve ULTRA 10

Non-return Valve ULTRA 10

Ultra performance protection against gas return: compact, quiet, ideal for low-pressure applications. Opening pressure approx. 4 mbar, up to 16 bar, G ½”

  • safety element: non-return valve [NV]
  • every non-return valve 100% tested
  • DIN EN ISO 5175-2
  • ultra-low opening pressures (approx. 4 mbar), ultra-low pressure drop
  • compact and light: 35 X 60 mm, 221 g, G ½”
  • minimal noise emission
  • dirt filter (100 μm) on gas inlet

Product of WITT

 

 

Loading...

Description

WITT non-return valves for reliable protection against dangerous reverse gas flow. Flow-optimised valve system causes very low pressure drop at minimal noise emission. Every non-return valve 100% tested.

Benefits

  • a spring-loaded non-return valve prevents back-feeding of gases which could lead to unwanted gas mixtures
  • low-pressure drops – using complex valve assembly with low opening pressures (ca. 4 mbar)
  • stainless steel filter (100 μm) in the gas inlet protects the non-return valve against dirt contamination, extending the service life
  • flow-optimised valve system for:

    – ultra low-pressure drop
– minimal noise emission

  • no leaks – using of a spring-loaded valve assembly with elastomer sealing
  • in accordance with DIN EN ISO 5175-2
  • available in brass or stainless steel (ES)
  • diverse applications – useful for many technical gases
  • reduce installation costs – the spring-loaded valve is not affected by gravity and may be installed in any orientation

Operation / Usage

  • non-return valves are used to protect equipment and pipelines against dangerous reverse gas flow.
  • Use is possible for applications according to EN 746-2
  • WITT non-return valves may be mounted in any position/orientation
  • in ambient temperatures above -20 °C / 68 °F and below 70 °C / 158 °F

Maintenance

  • annual testing of the non-return valve and body leak tightness is recommended
  • WITT is happy to supply special test equipment
  • non-return valves are only to be serviced by the manufacturer

Approvals
Company certified according to ISO 9001
Cleaned for Oxygen Service according to EIGA IGC Doc 13/12/E: Oxygen Pipeline and Piping
Systems