Slam Shut Valve HDS17

Slam Shut Valve HDS17

Shut-off device stops dangerous decomposition of acetylene in the high-pressure pipelines

highest quality from the world market leader
safety elements: flame arrestor [FA], temperature-sensitive cut-off valve [TV]
stops the dangerous decomposition of acetylene independent of inlet flow direction
every device is tested before delivery
BAM certified
50 X 152 mm, 1.797 g
up to 25 bar working pressure

Product of WITT 

 

Loading...

Description

WITT Automatic Quick Acting Shut-Off Devices (slam shut valves) for reliable protection against dangerous decomposition of acetylene in high-pressure pipelines in accordance with EN ISO 14114. Every Arrestor 100% tested.

The best Automatic Quick Acting Shut-Off Devices in the world

a pressure-sensitive piston valve stops explosive decomposition of acetylene
immediately cuts off the gas supply in case of decomposition of acetylene
Operation / Usage:

as an Automatic Quick Acting Shut-Off Device conforming EN ISO 14114 in high-pressure pipelines, which are directly supplied by more than six cylinders
WITT Automatic Quick Acting Shut-Off Devices may be mounted in any position/orientation
the maximum ambient/working temperature is 70 °C / 158 °F
Maintenance:

it is recommended that an annual body leakage test is performed
Automatic Quick Acting Shut-Off Devices are only to be serviced by the manufacturer
Approvals
Manufactured in accordance with EN ISO 15615
Company certified to ISO 9001

 